The introduction of distributed generators (DGs) that can utilize renewable energy is of prime importance to solve the energy and environmental issues. When a distribution network has a large number of DGs, voltage maintenance becomes a serious problem. To solve this problem, we had proposed the ‘voltage profile control method’ using reactive power control of DGs. However, the control is limited to continuous reactive power control so far, and tap control has not been considered. It is important that the conventional voltage control equipment such as the load ratio tap changer (LRT) or step voltage regulator (SVR) is utilized in order to enhance the control efficiency of the voltage profile control method. Therefore, in this paper, we develop a new method that can realize a cooperative work between inverters and tap control of LRT and SVR. The proposed method is tested in 8‐ and 24‐node model systems and its effectiveness is shown.