The battery voltage level is a critical parameter for Uninterruptible Power Supply (UPS) employed by Pagardewa compressor station. If batteries are faulty it could cause station shutdown. The UPS consists of batteries which should have a certain voltage level and it is placed in the temperature-specified battery room. The main purpose of this article is to measure battery voltage and room temperature then to display it continuously on a website and send notification messages if the voltage or temperature value is beyond the specified range. The system has been developed based on the Arduino Mega microcontroller which includes wifi for data communication. As a prototype, the monitoring system was applied to 8 of 108 batteries of the UPS during its daily normal operation. The voltage measurement test results showed that the monitoring system has an average measurement difference of 0.0082 V or equal to 0.1896 % when compared to that of by a commercial measuring instrument while the temperature measurement results in the battery room have a difference of 0.6 C o or equal to 3.03%. Hence, this prototype is potentially to be enhanced for all 108 batteries of UPS in order to prevent station shutdown.