Answers are grounded in this paper and cite their sources.
The ever-increasing utilization of sensitive loads in the industrial, commercial, and residential areas in distribution networks requires enhanced reliability and quality of supply. This can be achieved, thanks to self-healing features of smart grids that already include the control technologies necessary for the restoration strategy in case of a fault. In this paper, an analytical and global optimization model is proposed for the restoration problem. A novel mathematical formulation is presented for the reconfiguration problem reducing the number of required binary variables while covering more practical scenarios compared to the existing models. The considered self-healing actions besides the network reconfiguration are the nodal load-rejection, the tap setting modification of voltage regulation devices (incl. OLTCs, SVR, and CBs), and the active/reactive power dispatch of DGs. The voltage dependency of loads is also considered. Thus, the proposed optimization problem determines the most efficient restoration plan minimizing the number of de-energized nodes with the minimum number of self-healing actions. The problem is formulated as a Mixed-Integer Second Order Cone Programming (MISOCP) and solved using the Gurobi solver via the MATLAB interface YALMIP. A real 83-node distribution network is used to test and verify the presented methodology.
No takes yet. Share an insight, caveat, or question.
Sekhavatmanesh et al. (2018) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: