Quantifies the impact of duct shape and size on the flexural behavior of concrete beams, indicating structural performance implications.
Service ducts are frequently required in reinforced concrete (RC) beams for modern building services, yet their presence can alter structural performance and must be systematically assessed. This study aims to quantify the effects of duct orientation, size, and shape on the flexural behaviour of RC beams, with emphasis on first crack load, ultimate failure load, energy absorption, and ductility index. An experimental program was conducted on 39 RC beams, with three specimens per configuration: a control beam without ducts and beams with longitudinal ducts of circular, square, and diamond shapes, all tested under monotonic loading. Results show that the control beam reached a first-crack load of 7.62 kN and an ultimate load of 36.0 kN. Circular ducts caused the greatest reduction in first crack load (50.8–52.1%) and a 35.3% decrease in ultimate capacity, whereas diamond ducts increased ultimate load to 39.0 kN (+8.3%). Energy absorption improved significantly from 178.5 J to 499.0 J (+179.6%), while ductility indices remained relatively stable (1.40–1.54), varying between −3.4% and +6.2% compared to the control. These findings demonstrate that duct geometry plays a critical role in the structural performance of RC beams.