This paper investigates selective power transfer between users located in a power distribution line by the implementation of a multifrequency bus. Multifrequency power distribution implies the generation of additional power channels on the same distribution bus by combining two or more power transfers at different frequencies. To analyze the feasibility of this proposal, a point-to-point power transfer using a second frequency power channel in a power distribution line is proposed. To do that, an AC switching power source is required to inject that power in the grid, and an AC switching power sink to extract it and deliver it to the receiver load. Essentially, AC switching power injectors and extractors have the same circuit that consists of two inverters, one behaving as a voltage-source/sink and the other working as a current-source/sink. A proof-of-concept demonstrator is being developed to test the operation of the injector/extractor conversion block and the performance of the multifrequency bus at grid’s third harmonic.
No takes yet. Share an insight, caveat, or question.
Genaro-Muñoz et al. (2023) studied this question.