Answers are grounded in this paper and cite their sources.
This paper presents a new method for minimizing transmission line losses and improving voltage profile in a given system by adjusting control variables, i.e., tap position of transformers and reactive power injection of VAR sources. Transmission losses are considered as a function of voltage increments. The control variables and voltage increments are related by a modified Jacobian matrix. Linear Programming (LP) is used to calculate the voltage increments which minimize the transmission losses, and the adjustments of control variables are obtained by a modified Jacobian matrix. Since this method does not need any matrix inversion, it will save computational time and memory space.
No takes yet. Share an insight, caveat, or question.
Qiu et al. (1987) studied this question.