Randomized trial demonstrates effective suppression of high-frequency oscillation in MMC-based HVDC systems, suggesting improved grid stability.
In receiving-end modular multilevel converter (MMC)-based flexible high-voltage direct current (HVDC) grid-connected systems, high-frequency oscillation can significantly increase the peak values of the point of common coupling (PCC) voltage and grid current. To address this issue, this paper proposes a coordinated suppression strategy for high-frequency oscillation in receiving-end MMC grid-connected systems. First, an MMC impedance model is established based on harmonic linearization, and its frequency-domain interaction with the grid impedance is analyzed to clarify the formation mechanism of high-frequency oscillation and its main influencing factors. Then, considering the different roles of the voltage feedforward and current feedback channels in the target frequency band, a coordinated suppression strategy combining band-stop filtering in the voltage feedforward path with low-pass filtering and lead compensation in the current feedback path is designed. Hardware-in-the-loop experimental results show that the proposed method effectively identifies and suppresses high-frequency oscillation. Under the validated operating condition, the oscillation-induced peak increases in the PCC voltage and grid current are limited to within 20% and 12.5%, respectively, thereby suppressing further oscillation growth and reducing the risk of approaching the overvoltage and overcurrent protection thresholds.