Answers are grounded in this paper and cite their sources.
Demonstrates improved temperature calculations in UHV transformers, suggesting a better efficiency method.
In electromagnetic-fluid-thermal coupling calculations, conventional numerical methods often face challenges regarding computational accuracy and efficiency. To address the shortcomings of traditional methods under extreme operating conditions, such as over-excitation in ultra-high-voltage transformers, this paper proposes a reduced-order model (ROM) based on proper orthogonal decomposition (POD) and Kriging response surface methods for the rapid calculation of temperature fields under various operating conditions. First, a full-order computational model for electromagnetic-fluid-thermal coupling is established to analyze the nonlinear transfer law of hotspots under over-excitation conditions. Subsequently, a POD-Kriging reduced-order computational model is constructed. The results show that the maximum relative error of the ROM is only 2.92%, the single-step calculation time is shortened to 1.02 s, and the computational efficiency is 8894 times higher than that of the full-order model (FOM). This method significantly improves the calculation speed of the temperature field while ensuring high calculation accuracy.
No takes yet. Share an insight, caveat, or question.
Tian et al. (2026) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: