Investigates Legionella transmission risk from a cooling tower, suggesting effective mitigation strategies.
In the summer of 2023, a Legionnaires' disease outbreak occurred in Miyagi Prefecture, with a cooling tower identified as the source. Legionella bacteria were detected in the cooling tower at 680,000 CFU/mL (standard value: 1 CFU/mL), and 23 infections were reported within a 3 km radius. In this study, meteorological data from the specific period and GIS information of Osaki City were integrated into CFD modeling to calculate the distribution of Legionella within a 5 km radius of the source. Furthermore, a quantitative risk analysis was conducted, accounting for removal effects such as humidity and UV radiation during airborne transmission.
No takes yet. Share an insight, caveat, or question.
Wu et al. (2026) studied this question.