Experimental analysis demonstrates duct inclination enhances particle removal in low-velocity airflows, implying design improvements for filtration systems.
This study examined how duct inclination influences particle removal in a hybrid acoustic–electrostatic filtration system operating at low airflow velocities. The experiments were carried out in a 150 mm diameter air duct at airflow speeds of 0.50 and 0.75 m/s, with duct inclinations of 45° and 90°. Aerosol particles with properties similar to marine diesel exhaust, spanning a size range of 0.2–10 µm, were introduced at stable concentrations. Electrostatic voltages of 17.5 and 20 kV were applied, together with acoustic voltages between 100 and 200 V. Particle removal was evaluated using both size-resolved and overall collection efficiencies. The results show that duct inclination mainly affects the removal of fine and medium-sized particles. The largest differences were observed for particles around 1 µm in diameter, where the vertical duct increased collection efficiency by up to 27 percentage points at an airflow speed of 0.75 m/s. For larger particles in the 5–10 µm size range, high removal efficiency was achieved under all tested conditions, and duct orientation had a smaller influence on collection performance. Overall, the results confirm that duct inclination has a clear and measurable effect on the performance of hybrid acoustic–electrostatic filtration systems operating at low airflow velocities.