Demonstrates improved fire detection efficiency in warehouses, suggesting enhanced safety.
To address the problems of false negatives, false positives, and delayed response in traditional fire detection systems, this paper proposes a warehouse fire detection scheme based on multi-sensor information fusion. By constructing a ZigBee wireless sensor network and integrating temperature, CO concentration and smoke sensors, fire simulation data are collected in the warehouse. At the data processing level, an improved Grubbs criterion is innovatively adopted to eliminate outliers, and the median is used instead of the average to effectively suppress the same-side shielding effect. At the feature layer fusion stage, a BP neural network model optimized by the cosine decreasing inertia weight particle swarm optimization algorithm (CIW-PSO) is designed. By dynamically adjusting the learning factors (c1, c2) and inertia weight (w), the convergence speed and global optimization ability are significantly improved. At the decision-making level, a fuzzy logic reasoning mechanism is introduced to integrate multi-parameter membership functions, thereby reducing the probability of misjudgment. Field tests have verified that the system can achieve early fire warning in a 50 m × 100 m warehouse environment, with a false alarm rate reduced by 42% compared to a single sensor and a response time shortened by 35%, providing an efficient and reliable intelligent solution for warehouse fire safety.
No takes yet. Share an insight, caveat, or question.
Zhang et al. (2026) studied this question.
Synapse has enriched 5 closely related papers on similar clinical questions. Consider them for comparative context: