Investigates hybrid ventilation performance in monitor roofs, suggesting enhanced ventilation efficiency.
Weak wind conditions can substantially reduce the ventilation capacity of monitor-roof systems, especially in hot regions. To address this limitation, the present study examines a roof-assisted hybrid ventilation concept in which PV-supplied fans are combined with a conventional monitor roof and assessed through numerical flow simulations. The reference case consisted of a 1.2 m × 1.2 m monitor roof with a 0.3 m eave extension. A 20-fan array was placed along the roof opening, and the simulations compared two fan scales (0.3×0.3 m, 0.6×0.6 m) together with two discharge velocities (0.5 and 2 m/s). Outdoor wind conditions were represented by a power-law profile with an exponent of 0.143, and the reference wind speed at 10 m height ranged from 0.01 to 3 m/s. The results show that PV-powered fan assistance can effectively enhance ventilation under stagnant or low-wind conditions, when natural driving forces are insufficient. However, the contribution of the fans decreases as outdoor wind speed increases and wind-driven ventilation becomes dominant. Among the investigated cases, larger fans operated at higher outlet velocity showed the most stable and substantial improvement. The study demonstrates that integrating PV-powered fans with monitor roofs is a feasible approach for strengthening ventilation performance and environmental adaptability in industrial buildings.
No takes yet. Share an insight, caveat, or question.
Lin et al. (2026) studied this question.
Synapse has enriched 5 closely related papers on similar clinical questions. Consider them for comparative context: