Answers are grounded in this paper and cite their sources.
A novel di/dt triggered unidirectional self-powered DC circuit breaker is designed using either a normally-ON GaN HEMT or SiC JFET, with a low response time. Response time to fault is significantly reduced by eliminating PWM startup delay in the protection gate driver of GaN HEMT and SiC JFET. The circuit breaker prototype was built and experimentally demonstrated the interruption of fault currents up to 50 A at 400 V DC with response time as low as 600 ns.
No takes yet. Share an insight, caveat, or question.
Shankar et al. (2022) studied this question.