Answers are grounded in this paper and cite their sources.
Investigates performance of nonlinear programming algorithms for optimal power flow in low voltage networks, suggesting efficient formulation alternatives.
Three-phase optimal power flow (OPF) is a foundational mathematical optimization problem for power advanced distribution network management. In this work we study the application of nonlinear programming algorithms to a variety of state-of-the-art mathematical optimisation models for distribution OPF with 3 × 3 impedances on a library of 128 LV networks. We study numerical performance in terms of wall clock time as well as robustness. Specifically, we study a variety of voltage angle constraints, bounds and initialisation strategies that influence the performance significantly. Contrary to what has been observed for transmission networks, the power-voltage (polar) formulation is not necessarily the best formulation, and current-voltage is generally very competitive. We observe that power bases for per unit conversion need to be chosen small enough ( ≤ 1000 kW) to avoid inaccuracies. Numerical studies are performed for a set of 128 LV networks, using Ipopt and KNITRO.
No takes yet. Share an insight, caveat, or question.
Geth et al. (2026) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: