Comparative study reveals improved thermal performance in servers using pin-fin heat sinks, suggesting better cooling solutions.
Single-phase oil immersion is a promising alternative to air cooling for high-power servers, but the high viscosity of dielectric fluids amplifies the bypass flow around the CPU heat sink via the adjacent random-access memory (RAM) channels, degrading thermal performance. A simplified hydraulic-thermal analysis shows that this bypass penalty cannot be eliminated by reducing the fin pitch of a rectangular-fin heat sink alone. A staggered pin-fin heat sink is therefore proposed, with pin diameter D, longitudinal pitch Sd, and transverse pitch St optimized by three-dimensional CFD using PAO-6. The optimum geometry is D = 2.8 mm, St = 6 mm, Sd = 8.45 mm. The heat sink is fabricated and tested in a commercial server at oil inlet temperatures of 30–45 °C and flow rates of 3–6 LPM. At 3 LPM, the pin-fin immersion server reduces the CPU thermal resistance by 22.29% relative to a rectangular-fin immersion server using the same oil, and by 38.37% relative to an air-cooled server. The partial Power Usage Effectiveness (pPUE) reaches 1.015, an 88.09% improvement over the air-cooled baseline (pPUE = 1.126), confirming that pin-fin geometries effectively mitigate the bypass penalty in single-phase oil immersion cooling.