Answers are grounded in this paper and cite their sources.
Shows a stable flow rate in prefabricated buildings, indicating a novel solution for ventilation balancing.
Spatial constraints in prefabricated buildings render conventional constant air volume (CAV) valves difficult to install and commission. To address this, this study presents a compact, passive CAV valve that integrates a symmetrical Tesla-inspired flow channel with an adaptive spring-loaded core to autonomously modulate resistance without external power or sensors. Computational fluid dynamics (CFD) simulations were employed to optimise the structural parameters and analyse the flow field characteristics. Numerical analysis revealed that the valve’s flow field characteristics and flow coefficient (CV) are primarily governed by the displacement (x) between the valve core and baffles, while being relatively independent of inlet pressure and baffle angle. Furthermore, numerical analysis indicates that the aerodynamic force on the valve core exhibits a strong linear relationship with displacement x (R2≈0.99). A 3D-printed prototype was subsequently constructed to validate the numerical model under realistic operating conditions. Experimental results demonstrate that the valve maintains a stable flow rate with a control error within ±5% across a pressure difference range of 60–230 Pa. This research confirms the feasibility of applying Tesla valve principles to flow regulation and provides a robust, space-efficient solution for ventilation balancing in modern industrialised construction.
No takes yet. Share an insight, caveat, or question.
Qiu et al. (2026) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: