Assesses frequency and RoCoF estimation in power systems, indicating improved accuracy with a new method.
An observer based adaptive detection methodology (ADM) is proposed for estimating frequency and its rate of change (RoCoF) of the voltage and/or current measurements acquired from an instrument transformer. With guaranteed convergence and stability, the proposed methodology effectively neutralizes the effect of the measurement distortions like harmonics, decaying DC components and outliers by adding its counter negative. It is robust to noise statistics, performs well while encountering step changes in amplitude/phase and is demonstrably superior to its precursors as established by test results. A benchmark IEEE NETS/NYPS 16 machine 68 bus power system has been used for performance evaluation of robust ADM against its precursors and scaled laboratory setup based on OP5600 multiprocessors was used for establishing its real-time applicability.
No takes yet. Share an insight, caveat, or question.
Mir et al. (2021) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: