Answers are grounded in this paper and cite their sources.
Evaluates low-carbon performance in transformers, indicating potential for improved green procurement.
In green procurement, the full life cycle concept is not yet well established, and existing low-carbon evaluation systems remain insufficiently robust. To address these gaps, this study develops a low-carbon assessment method for transformers that centers on the carbon footprint (CF) and incorporates life cycle low-carbon indicators. A grading approach based on the distribution characteristics of the samples is used to classify the CF, and this classification is combined with a low-carbon indicator score to form a comprehensive evaluation system. The method was applied to eighteen transformers: 10 kV and eight spanning 10 to 1000 kV. The results show strong consistency between the CF and the low-carbon indicator scores, with clear stepwise differences in the overall evaluation outcomes. The operation and maintenance phase consistently dominates, accounting for at least 45.24% of the total and serving as the key driver of low-carbon performance. The raw-material acquisition phase contributes 10.95–28.57%, its highest value is 2.93 times its lowest, which substantially widens the differences among products. This study presents a grading evaluation method that integrates the CF and life cycle low-carbon indicators, enabling clear differentiation of product carbon levels and providing decision support for green transformer procurement and for the green transformation of the industry.
No takes yet. Share an insight, caveat, or question.
Bai et al. (2026) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: