In this study, the effects of the barrier added to the kitchen hood suitable for central ventilation systems on the performance of odour extraction are investigated. For this purpose, the hood used in the kitchens of the buildings with central ventilation systems has been selected. Taguchi L18 (61x31) experimental design method was used to optimize the odour extraction performance of the hood and to examine it both experimentally and statistically. Kitchen hoods with different size barriers have been created with the selected method. The experiments were conducted in the test room in accordance with international standards. When the results of the experiment were examined, it was observed that the odour extraction performance of the hoods created in the experiments was the best 97.1% and the worst was 69.4%. When the signal/noise ratios of the experiments carried out with different size barrier and flow parameters were examined, the most ideal levels for C2 were determined as A6B3. When the Anova results were examined, it is determined that the most effective parameter for C2 was barrier (cm) with 76.01% and flow rate (m3/h) with 21.24%. By means of the barrier added to the hood, higher odour extraction performance has provided.
No takes yet. Share an insight, caveat, or question.
ÖZBAKIŞ et al. (2020) studied this question.