July 26, 2026Recent Advances in Electrical & Electronic Engineering (Formerly Recent Patents on Electrical & Electronic Engineering)

A Hybrid VMD-SVM Multi-Feature and Wavelet Modulus Maxima-Based Method for Fault Line Identification and Location in Distribution Networks with Single-Phase Ground Faults

View Full Paper
Ask AI
Bookmark
Share

Authors

LDLe DongSHShuang HeRZRui Zhao

Discussion

Loading...

Member takes

Overview

Randomized trial demonstrates enhanced fault identification accuracy in distribution networks, suggesting improved reliability.

Key Points

  • This research aims to develop an integrated method for accurate identification and location of single-phase ground faults in distribution networks.
  • Fault type identification using sequence component characteristics prior to line selection.
  • Feature construction based on variational mode decomposition optimized by the Sparrow Search Algorithm.
  • Utilization of a single-ended fault location method based on wavelet transform modulus maxima.
  • Achieved fault-line selection accuracy of 98.4%.
  • Location error for a 100 km line is less than 1.673%.
  • SVM-based approach outperforms conventional fuzzy theory methods under complex fault scenarios.

Cite This Study

Dong et al. (2026) studied this question.

synapsesocial.com/papers/6a65a91fd3aea3239cd7923dhttps://doi.org/10.2174/0123520965482463260708100410