The effects of renovation and return air-distribution systems on the exposure of occupants in a commercial building to asbestos under worst–case conditions were evaluated. General area samples were collected in four test and five control locations over five days. The presence or absence of construction or of a suspended ceiling acting as a return air plenum were tested for effect on airborne concentrations of asbestos. To maximize the likelihood of detecting measurable effects, all sampling was performed in areas with damaged asbestos-containing surface material. Air samples of 1200–2400 L were collected on 0.45 micron, 25 mm cellulose acetate filters using high-volume pumps. Samples were analyzed by transmission electron microscopy using a direct preparation technique with a lower detectable limit of 0.002 structures per cubic centimeter (s/cm3). Airborne concentrations of asbestos were consistently less than 0.008 s/cm3, with only 15 of 60 samples having detectable levels. The highest concentrations were found in the construction area (0.007 s/cm3) and in the area with no suspended ceiling (0.008 s/cm3), though tests of statistical significance for these effects were equivocal. Although limited in scope, study results are consistent with others using similar methods, and indicate that general building occupants are unlikely to be exposed to airborne concentrations of asbestos exceeding background.