Answers are grounded in this paper and cite their sources.
Chapter 8 : This chapter focuses on anomaly-resistant decentralized state estimation for wide-area power systems, and addresses challenges from measurement anomalies (outliers, bad data) and high computation/communication burdens of centralized frameworks. Traditional state estimation methods lack robustness against anomalies and struggle with large-scale system deployment. To solve these issues, the chapter proposes a decentralized scheme integrated with the minimum error entropy with fiducial points (MEEF) criterion. The wide-area power system is divided into non-overlapping areas, with local measurements (from SCADA and PMU) and edge measurements (from inter-area transmission lines) collected separately. An augmented model (which incorporates local prediction and measurement information) is constructed via unscented transformation and statistical linearization to improve data redundancy. An MEEF-based cost function is designed to enhance anomaly resistance, and local estimates are obtained through fixed-point iteration. Edge measurement information updates local estimates to improve overall accuracy. The experiment carried on IEEE 14-bus system through three scenarios (centralized vs. decentralized comparison, resistance to non-Gaussian outliers, and bad data) validates the scheme&s;s effectiveness since it outperforms centralized methods in computational efficiency (average 15–18 ms per iteration) and maintains stable estimation accuracy amid various anomalies.
No takes yet. Share an insight, caveat, or question.
Qu et al. (2024) studied this question.