Answers are grounded in this paper and cite their sources.
Grid harmonic interactions due to aggregated flyback micro‐inverters are investigated in this study. An impedance‐based model based on the Norton model of flyback micro‐inverters, which are with quasi‐resonant peak‐current control, is obtained by adopting the small‐signal modelling approach. As a supplement to the existing output impedance modelling of string inverters with linear controllers, further study on micro‐inverters under non‐linear control is addressed in this study. Based on the derived impedance model, the admittance matrix of aggregated micro‐inverters connected to the grid is formulated and the impedance‐based analysis of the system stability is also presented. Consequently, by modelling the output admittance of the quasi‐resonant peak‐current controlled flyback micro‐inverters, harmonic interactions with a distorted grid can be effectively forecasted. Results obtained from modelling, analysis and verifications have shown that the proposed method is a simple and valid way of dealing with the harmonic quasi‐resonance problems.
No takes yet. Share an insight, caveat, or question.
Wang et al. (2017) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: