Answers are grounded in this paper and cite their sources.
Inter-area oscillations is a potential threat for uncontrolled islanding leading to power system blackout. Based on the severity of inter area oscillations, three control strategies, namely: 1) device based control; 2) operational based control; and 3) structural based control approaches can be applied. Emergency controlled islanding is a structural based method consisting of three sub-tasks denoted as “when,” “where,” and “how” to intentionally separate a power system. In this paper, regarding the task of when, an intelligent out-of-step predictor for inter-area oscillation is proposed. It is shown that early prediction of power system trend toward inter area instability can be used as a criteria for handling the issue of when. For this purpose, the criterion of the speed-acceleration which is earlier developed for out-of-step of single machine is extended for out-of-step of inter-area oscillations. In this approach, based on the concept of center of inertia, coherent areas oscillating against each other are represented by two equivalent machines from which extended speed-acceleration locus curve is derived. The slope of the extended speed-acceleration locus curve can be used as a criterion for predicting system trend toward uncontrolled separation. The main feature of the proposed criterion is its independency from system modeling and just relying on on-line data obtained from WAMS. The proposed approach is applied on IEEE 39 bus test system and Iran power system with promising results.
No takes yet. Share an insight, caveat, or question.
Salimian et al. (2016) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: