This is the authors' abstract. We don't add key points for this paper.
To mitigate the vulnerability of distribution grids to severe weather events, some electric utilities use preemptive de-energization as the primary line of defense, causing significant power outages . In such instances, networked microgrids could improve resiliency and maximize load delivery, though the modeling of three-phase unbalanced network physics and computational complexity pose challenges. These challenges are further exacerbated by an increased penetration of uncertain loads. In this paper, we present a two-stage mixed-integer robust optimization problem that configures and operates networked microgrids, and is guaranteed to be robust and feasible to all realizations of loads within a specified uncertainty set , while maximizing load delivery. To solve this problem, we propose a cutting-plane algorithm, with convergence guarantees, which approximates a convex recourse function with sub-gradient cuts. Finally, we provide a detailed case study on the IEEE 37-bus test system to demonstrate the economic benefits of networking microgrids to maximize uncertain-load delivery.
Answers are grounded in this paper and cite their sources.
No takes yet. Share an insight, caveat, or question.
Moring et al. (2024) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: