Communication delays and false data injection attacks pose significant threats to the frequency control of automatic generation systems. This paper presents a Golden Jackal Optimizer (GJO)-enhanced frequency-shifted internal model control (FIMC) scheme aimed at addressing these challenges in a dual-area thermal power system. The FIMC approach employs a pole and zero shifting variable that acts as a system robustness indicator. The paper determines an analytical search range for this variable using the Routh-Hurwitz criteria, which were later utilized by GJO. The robustness and performance of the GJO-tuned FIMC are tested against random and step load disturbances, as well as system nonlinearities. The paper models various false data injection threats, assessing the effectiveness of the GJO-tuned FIMC in neutralizing these threats under inherent communication delays. Finally, the proposed strategy is verified in real-time through hardware, employing the OPAL-RT platform. The results are compared with a recent strategy, underscoring the advanced efficacy of the proposed approach.