Answers are grounded in this paper and cite their sources.
This paper presents the design of a direct-type adaptive control structure for current regulation of a single-phase grid-tied Voltage-Source Inverter (VSI) with an LCL filter under very weak grid condition. The initial content of this work was previously published, where the controller was presented and its discrete-time stability proof was provided. Power converters connected to weak grids bring challenges to the control system, since the grid can change abruptly from a strong to a very weak condition , degrading system power quality. This study evaluates the feasibility of a RMRAC-based robust adaptive Super-Twisting Sliding Mode controller for current control of VSI when the grid inductance changes substantially, from 0 mH (strong grid) to 10 mH (very weak grid). To show the benefits of the control strategy and its robustness, hardware-in-the-loop (HIL) simulation results are presented, comparing its performance with two other controllers..
No takes yet. Share an insight, caveat, or question.
Hollweg et al. (2022) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: