Answers are grounded in this paper and cite their sources.
One of the more difficult problems to solve in industrial plants is how to identify and eliminate ground faults in a high-resistance ground (HRG) system. This is because ground-fault conditions in these systems do not draw enough current to reliably trigger fault current sensors in the drive. This article develops an approach to identify the ground-fault location in HRG systems using voltage sensing, rather than current sensing techniques, inside an adjustable speed drive (ASD). This approach consists of a simple analog circuit and digital signal processing technique to detect a fault condition, as well as to identify the fault location, be it on the load motor side, inside the ASD, or ac line side. The use of this ground-fault identification method is also extended and discussed for application to multiple drive lineups.
No takes yet. Share an insight, caveat, or question.
Wei et al. (2013) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: