Answers are grounded in this paper and cite their sources.
Estimation of building cooling load is of critical importance for achieving energy efficiency and thermal comfort in buildings. The computer-based methods for cooling load estimation are expensive while most of the inverse models are complex and require adequate time to train the models. In this paper, a multiple linear regression model was developed using the concept of Taguchi orthogonal array. The model developed has high performance based on the computed 2 . The cooling load model developed was validated using EnergyPlus thermal simulation. Employing the cooling load model, the cooling load of the site office building was 10.48 kW while the EnergyPlus simulated result was 10.29 kW. The RMSLE between the predicted and the EnergyPlus simulated result is 0.017 which indicates that the model developed has high predictive power. The proposed model has high inference and prediction powers and could be used for predicting cooling load of office buildings of Bayero University Kano (BUK) or any other building with similar attributes.
No takes yet. Share an insight, caveat, or question.
Ibrahim U. Haruna (2022) studied this question.