Answers are grounded in this paper and cite their sources.
In this paper, the hardware and software design and implementation are proposed for the wide-area damping control (WADC) strategies. First, the hardware-in-the-loop (HIL) real-time (RT) simulation system based on the RT-Lab is established as the closed-loop test platform for the WADC applied in multi-machine interconnected power system. The hardware, which contains the microcontroller, the peripheral analog to digital converter, and the digital to analog converter, are developed based on the AVR 32-bit development board. Three WADC algorithms, i.e., the phase-compensation, the delay-dependent state-feedback, and the dynamic output-feedback method, are introduced. Then, the software design of the above algorithms is proposed and the bilinear transform method is employed to get the discrete-time model of the controllers. The flowchart of each algorithm is designed for the implementation in the environment of hardware. The designed WADC is embedded in a real-time power system. Finally, case studies are carried out based on the HIL real-time simulation system. The proposed control concept and WADC design methods are validated by considering the big/small disturbance and the signal time-varying delay. The effectiveness of the proposed HIL closed-loop test system is also confirmed.
No takes yet. Share an insight, caveat, or question.
Li et al. (2016) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: