Answers are grounded in this paper and cite their sources.
Comparative simulation study demonstrates higher thermal efficiency of earth-air heat exchangers in hot-arid versus cold climates, indicating greater suitability for arid building cooling.
This study presents a novel and reliable comparative model developed using MATLAB/Simulink to analyze and design Earth-Air Heat Exchanger (EAHE) systems under two distinct climate types: hot-arid and cold-continental. The model stands out for its effectiveness, relying on climate data to evaluate system performance-making it a valuable tool for designers and researchers alike. It has been experimentally verified. Two contrasting case studies were chosen: Baghdad (hot-dry) and Gothenburg (cold continental). Experimental air temperature data were collected and used as input for simulation. The results demonstrate distinct thermal behaviors in each region. At 5 m depth, Baghdad’s soil stays hot (31.3–30.1 °C), while Gothenburg’s remains cooler and stable (12.09–11.55 °C). Performance simulations showed that the EAHE system in Baghdad achieved 602 W cooling in July and 728.3 W heating in December. In Gothenburg, it delivered 478.52 W cooling in July and 447.97 W heating in January. These results confirm higher EAHE effectiveness in hot-arid regions, with Baghdad outperforming Gothenburg by 20.5 % in cooling and 38.5 % in heating. Moreover, Pipes of 40–50 m yielded significant thermal gains-up to 13.83 °C in Baghdad and 10.47 °C in Gothenburg-without major cost increase. Notably, Baghdad showed a 24.3 % higher temperature differential, reaffirming system suitability in arid climates.
No takes yet. Share an insight, caveat, or question.
Ali et al. (2025) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: