Answers are grounded in this paper and cite their sources.
Appropriate design of a substation grounding grid keeping in view of safety of equipment and personnel working area in or walking close to the substation is of great importance. Several steps are involved to design and developed a safe, effective and optimized grounding grid. IEEE Standard 80-2000 explains the terminologies, definitions, formulas and act as an important guide for substation grounding grid design. To date a number of substations grounding grid design intelligent software have already been developed by engineers of many commercial enterprises which takes well care of safety, reliability, continuity of services and optimization of the design. Such a software, e.g., Electrical Transient Analyzer Program (ETAP) has been utilized in this study which has achieved optimization in substation grounding grid design ensuring safety of personnel and equipment. The study utilized the Finite Element Method (FEM) of Ground Grid System (GGS) module of ETAP in combination with Sverak's variable space technique and showcased that 63.88% copper saving of ground rods could be achieved in comparison with a reference study of substation grounding grid. The method thus has become a very effective tool in substation grounding grid optimization.
No takes yet. Share an insight, caveat, or question.
Hossain et al. (2021) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: