Answers are grounded in this paper and cite their sources.
Voltage sag produced by an induction motor starting current is a main cause of sensitive equipment dropout. The use of a motor starter reduces the voltage sag depth but increases its duration. The subsequent connection to full voltage produces a new sag separated from the first one by a few seconds. A simple method is presented that allows us to transform the information of starting current/time characteristics to voltage sag depth/time characteristics that are directly comparable with the sensitive equipment susceptibility curves (CBEMA and other curves). The method also allows one to consider motor repetitive starts and different starting cycles.
No takes yet. Share an insight, caveat, or question.
Zapata et al. (2002) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: