This is the authors' abstract. We don't add key points for this paper.
Existing theories, specification, and standards relating to the application of dry-type distribution transformers for solid-state applications are discussed. The criteria for selecting the proper transformer for several types of solid-state loads, such as UPSs, rectifiers, variable-speed drive systems, etc. are discussed. A significant set of computer-generated calculations that show the behavior of dry-type distribution transformers of various sizes and conductor configurations under both sinusoidal and nonsinusoidal conditions is presented. It is readily seen that improper selection of a transformer for a solid-state application may result in a serious reduction in efficiency as well as a large increase in temperature rises with detrimental effect on the expected life span of the transformer. A few experimental results from tests carried out on several transformers are presented.>
Answers are grounded in this paper and cite their sources.
No takes yet. Share an insight, caveat, or question.
Kerszenbaum et al. (1991) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: