A theoretical analysis of the method proposed by the AIEE committee on electrical machinery for measuring the negative-sequence reactance of synchronous machines is presented in this paper. The analysis proves that the method leads to a correct measurement of the negative-sequence reactance for the operating condition most frequently met in applying the method of symmetrical components, but that the method of measurement does not determine the correct negative-sequence reactance of the machine for the operating conditions used in the proposed AIEE test. The results of experimental tests are given to verify the theory presented.
No takes yet. Share an insight, caveat, or question.
W. A. Thomas (1936) studied this question.