This paper presents a novel partial-discharge (PD) recognition method based on the extension theory for high-voltage cast-resin current transformers (CRCTs). First, a commercial PD detector is used to measure the three-dimensional (3-D) PD patterns of the high-voltage CRCTs, then three data preprocessing schemes that extract relevant features from the raw 3-D-PD patterns are presented for the proposed PD recognition method. Second, the matter-element models of the PD defect types are built according to PD patterns derived from practical experimental results. Then, the PD defect in a CRCT can be directly identified by degrees of correlation between the tested pattern and the matter-element models which have been built up. To demonstrate the effectiveness of the proposed method, comparative studies using a multilayer neural network and k-means algorithm are conducted on 150 sets of field-test PD patterns of 23-kV CRCTs with rather encouraging results.
Answers are grounded in this paper and cite their sources.
No takes yet. Share an insight, caveat, or question.
Wang et al. (2005) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: