This paper presents a method to design a control system for a three-phase voltage source converter (VSC) that connects a renewable energy source to the utility grid through an outputL-type orLCL-type filter. The well-knownabc/dqtransformation method creates coupling terms that are visible and can readily be canceled in theL-type filter. Such terms, however, are very complicated when anLCLfilter is used. This paper, first revisits the derivation of the decoupling control method for anL-ype output filter and then, for the first time, derives the decoupling terms for anLCL-type filter. Having successfully decoupled the real and reactive power loops, feedback controllers are presented and designed to achieve desirable performance. The proposed controller provides active damping of theLCLresonance mode, robustness with respect to grid frequency, and impedance uncertainty. Moreover, a new controller is designed to improve the startup transient of the system. The methodology used in this paper is inspired from the feedback linearization theory and it provides a clear design method for the nonlinear systems. Simulation results are presented to confirm the analytical results.
No takes yet. Share an insight, caveat, or question.
Khajehoddin et al. (2011) studied this question.
Synapse has enriched 5 closely related papers on similar clinical questions. Consider them for comparative context: