This is the authors' abstract. We don't add key points for this paper.
One-line fault location techniques of intermittent ground fault points on nongrounded distribution lines are necessary to supply steady electric power for customers. This paper proposes a novel method that uses frequency spectra of transient waveforms at a sending end when an intermittent ground fault occurs. In this method, if a ground fault position differs, it causes a different frequency spectrum pattern for the current or voltage transients at a send end (decided by surge reflection phenomena between the sending end and the ground fault point). Comparison between experimental data of one-line ground fault tests on a simulated overhead line (373 m line length, two branch points) and digital simulation analyses shows that the grounded capacitance of a power source transformer was useful in locating the ground fault point.
Answers are grounded in this paper and cite their sources.
No takes yet. Share an insight, caveat, or question.
Kikuchi et al. (1997) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: