A transformer is one of the most important units in power networks; thus, fault diagnosis of transformers is quite significant. In this paper, the frequency-response analysis, deemed as a suitable diagnostic method for electrical and/or mechanical faults of a transformer, is employed to make a decision over a defective phase. To deal with wideband frequency responses of each phase, a synthetic spectral analysis is proposed, which augments low- and medium-frequency components, and equalizes the frequency intervals of a resulting combined curve by a log-frequency interpolation. Furthermore, for discriminating a defective phase through computing overall amounts of deviation with other phases, the two well-known criteria and three proposed criteria are examined with experiment data. The overall diagnosis results show that the proposed criterion discriminates a defective phase with the highest average hit ratio among all of the provided criteria for selected faults.
No takes yet. Share an insight, caveat, or question.
Kim et al. (2005) studied this question.
Synapse has enriched 2 closely related papers on similar clinical questions. Consider them for comparative context: