A 1 MVA single phase high temperature superconducting (HTS) transformer was fabricated and a part of experimental test for characteristics of the transformer was performed. The rated voltages of primary and secondary of the HTS transformer are 22.9 kV and 6.6 kV respectively. BSCCO-2223 wire was used for HTS windings whose shapes are double pancake arranged reciprocally. Single HTS wire for primary windings and 4 HTS wires for secondary windings were used considering the rated current of the transformer. Four HTS wires in secondary windings were transposed at the connection between double pancakes 3 times. The electrical insulation and transport current test were performed at 77 K using liquid nitrogen. The rest of the test for the characteristics of the transformer is in progress.