Answers are grounded in this paper and cite their sources.
A short circuit from one pole to ground on a bipolar overhead dc line can produce an overvoltage factor as high as 2.2 per unit on the unfaulted pole, which may cause flashover of line insulation, thus converting a monopolar fault into a bipolar one. This is undesirable because a bipolar fault causes a greater disturbance to the power system than does a monopolar fault.
No takes yet. Share an insight, caveat, or question.
Edward W. Kimbark (1970) studied this question.