A simple formula is developed to predict the sparking potentials of SF6 and SF6-gas mixture in uniform and non-uniform fields. The formula has been shown to be valid over a very wide range from 1 to 1800 kPa·cm of pressure and electrode gap separation for mixtures containing 5 to 100% SF6. The calculated values are found to be in good agreement with the previously reported measurements in the literature. The formula should aid design engineers in estimating electrode-spacings and clearances in power apparatus and systems.
No takes yet. Share an insight, caveat, or question.
Nema et al. (1982) studied this question.