Answers are grounded in this paper and cite their sources.
The three-dimensional FEM electric field calculation model of a fiber glass-reinforced plastic (FRP) hot stick during live-line work, which was elaborated in a previous study, could well explain some features of the flashovers that occurred during a series of cold fog tests at CIGELE. These tests have achieved the most reliable reproduction of four separate FRP hot stick flashover incidents in Canada at a voltage stress of 105 kV/m at -1.04°C, Relative Humidity (RH) of 109 % with visible fog and 2.8 μg/cm2 Equivalent Salt Deposit Density (ESDD). However, at the incident site, the geometry is different from that of the laboratory tests. In this paper, a three-dimensional electric field calculation model of a FRP hot stick during live-line work based on the finite element method is proposed to account for the geometry of the Manitoba site incidents at 500-kV. Moreover, the influence of the tower, phase conductors and shield wires on the potential and electric field distribution around an FRP hot stick during live-line work is studied.
No takes yet. Share an insight, caveat, or question.
Ghassemi et al. (2015) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: