Answers are grounded in this paper and cite their sources.
Breakdown (BD) characteristics in vacuum are strongly dependent on the electrode surface conditions, such as surface roughness. However, there is little known concerning the details of the relationship between the surface roughness and BD conditioning effect. In practical application, it is important to clarify how the surface roughness affects the breakdown conditioning characteristics, especially for the non-uniform field configuration. This paper discusses the effect of surface roughness on breakdown conditioning characteristics under non-uniform electric field in vacuum under applications of negative standard lightning impulse voltage. For this purpose, we examined the BD conditioning of a rod-to-plane electrode made of SUS304 and Cu-Cr. The surface roughness of Rais controlled from 0.3 to 2.5 mum. Experimental results revealed that the enhancement of surface roughness of electrodes increases the number of BD to complete the conditioning effect. We explained the results from the observed results of the electrode surface. Consequently, we could clarify the effect of surface roughness on the conditioning effect under non-uniform electric field in vacuum quantitatively.
No takes yet. Share an insight, caveat, or question.
Kato et al. (2007) studied this question.