Answers are grounded in this paper and cite their sources.
Two basic schemes for thyristor-controlled static compensators are described, namely, thyristorswitched capacitors (TSC) and thyristor-controlled reactors (TCR). A more advanced scheme using a combination of TSC and TCR is presented. It is shown that this combination gives a greater degree of flexibility in the designing of a compensator. The paper also briefly describes the control system in a compensator comprising both thyristor.controlled reactors, thyristor-switched capacitors and reactors (TSR). One method to damp power oscillations, using TSC with a certain control strategy, is presented. The problem of unbalanced loads and load balancing methods using TSC and TCR aie discussed. It is shown that the combined system (TSC/TCR) generates very low harmonics, because the TSC does not generate any harmonics. Finally, some pictures from the first installations comprising both TSC and TCR are shown
No takes yet. Share an insight, caveat, or question.
S. Torseng (1981) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: