A case of power system harmonic resonance that resulted in failure of 13.8 kV switchgear and consequent plant losses is documented. Calculations of the power system natural frequencies are given for various power system configurations of supply reactance, motor reactance, and system shunt capacitance. Sources of harmonic current are identified, methods of measuring harmonic current and voltage levels throughout the system are described, and results of the power system harmonic current and voltage survey are reported. Also described is the corrective action taken to prevent a recurrence of harmonic resonance.>
No takes yet. Share an insight, caveat, or question.
G. Lemieux (1990) studied this question.