Answers are grounded in this paper and cite their sources.
Trace hydrogen sulphide (H 2 S) could reflect the severity of insulation faults in gas‐insulated switchgear (GIS), therefore, accurate and fast detection of low‐concentration H 2 S is important for on‐line monitoring, fault diagnosis, and state evaluation in GIS. Ag‐Ti 3 C 2 T x chemiresistive‐type sensors were fabricated via drop‐coating with self‐reduction synthesised Ag‐doped Ti 3 C 2 T x . The as‐prepared sensors exhibited an excellent sensitivity and selectivity to H 2 S with an extremely low detection of limit of 18.57 parts per billion (ppb) at 25°C (room temperature). The response of Ag‐Ti 3 C 2 T x sensor to 10 parts per million (ppm) H 2 S was enhanced ∼12 times than that of the pristine Ti 3 C 2 T x sensor. The compositing of Ti 3 C 2 T x with Ag nanoparticles (NPs) enabled the fast response/recovery time for H 2 S detection. Further analysis found that the enhanced H 2 S sensing performances could be attributed to chemical sensitisation, adsorbed oxygen species regulation and high Brunauer–Emmett–Teller (BET) surface area. This study paves the way for Ag‐Ti 3 C 2 T x as room‐temperature sensing materials to detect low‐concentration H 2 S in GIS.
No takes yet. Share an insight, caveat, or question.
Zeng et al. (2023) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: