Distribution networks (DNs) gradually become more active and flexible with the massive integration of renewable resources. The conventional protection methods are unsuitable for the promising active DNs. This paper proposes a protection scheme on the basis of measured impedance, which includes an impedance differential method and an inverse-time low-impedance method. The former approach identifies fault instant and provides time reference for the exchanged data. As primary protection, it is able to clear different types of faults as soon as possible. The latter method operates in an automatic coordination way with inverse-time characteristic. It can be used as backup protection or provide protection for single-end lines alone. Both of the methods are independent of operation modes and are able to clear faults with high sensitivity. The efficiency of the protection scheme is validated by PSCAD/EMTDC.