Answers are grounded in this paper and cite their sources.
A key challenge associated with a grid-forming (GFM) inverter based resource (IBR) is its behavior during severe grid disturbances: since a GFM inverter regulates voltage in the fast timescale instead of current or power, it may experience a transient overload of current, power and/or energy during a severe grid disturbance. While many promising control strategies for overload ride-through have been proposed over the past two decades, transient stability of the system during and after the transition to an overload ride-through control mode remains difficult to guarantee. In this article, a novel overload ride-through control strategy is proposed for a system of grid-forming inverters that takes both self-protection and system-wide transient stability into account. A proposed system-level supervisory control uses slow communication to pre-emptively assign a set of local ride-through control parameters to individual GFM IBR, including a current-limiting virtual reactance, that guarantees that synchronism is still preserved for any set of anticipated grid disturbances. At the core of the supervisory control lies a Lyapunov-function-based routine capable of establishing a strong, albeit conservative, transient stability guarantee for the system. The proposed overload ride-through control strategy is validated via numerical integration of a reduced-order model, as well as through detailed electromagnetic transient (EMT) simulation.
No takes yet. Share an insight, caveat, or question.
Hart et al. (2022) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: