This paper provides an experimental discussion on zero-voltage-ride-through (ZVRT) capability of a phase-shifted pulsewidth-modulation distribution static synchronous compensator (D-STATCOM) using the modular multilevel cascade converter based on single-star bridge cells (SSBC). The cluster-balancing control producing a significant effect on the ZVRT capability is modeled and analyzed with focus on either a low-pass filter (LPF) or a moving-average filter (MAF) to attenuate the 100-Hz (double the line frequency) component inherent in each dc capacitor voltage. The cluster-balancing control using the MAF is better in transient performance than that using the LPF. A three-phase downscaled SSBC-based D-STATCOM rated at 150 V and 10 kVA is designed, constructed, and tested to verify the ZVRT capability under the severest single-, two-, and three-phase voltage sags with a voltage depth of 100%. Experimental waveforms show that the STATCOM continues operating stably as if no voltage sag occurred.
No takes yet. Share an insight, caveat, or question.
Ota et al. (2014) studied this question.
Synapse has enriched 4 closely related papers on similar clinical questions. Consider them for comparative context: